HVAC Low Ambient Control (Pressure Switch) Video

Split system serving a server room. Condenser fan controlled by pressure switch.

Add to Yahoo MyWeb Add to Yahoo Buzz Add to Yahoo Bookmarks Stumble on StumbleUpon Add to Reddit Add to Google Bookmarks Add to Newsvine Add to MySpace Add to Windows Live Add to Furl Add to Fark Add to Facebook Submit to Digg Add to Delicious Add to Blinklist

Comments on "HVAC Low Ambient Control (Pressure Switch)"

@theASEtech I think ...
@theASEtech I think the refrigerant was migrating to the cooler compressor on the off cycle when the ambient was low (nights & mornings). The compressor may have tried to start against this liquid. The fuse may have blown because of the high amp draw because of this start up situation. I have installed? a crank case? heater (the wrap around kind) and shall monitor it. Dave Van West.

i didn't get what ...
i didn't get what was the problem? of the blown fuse can you explain it to me please i'm new on this career trying to learn about a hvac career probably is been a long time since you did this video but i just saw it thanks it is great video

Can you please ...
Can you please explain the purpose of the air line coming off of the pressure switch where it T's off to the gas valve and the burner box? I don't understand? the purpose of this air line going to the gas valve. Even my HVAR instructor can't answer this question, and I'm about Googled to death.

@Straycurrent ...
@Straycurrent Thanks for the? question. I use a blue sealant called "Leak Lok." I apply it ti the male threads. And haven't had a problem. Maybe the specific tee adaptor you used was defective? I have had that happen with Schrader cores in the past.

Van - thanks for a ...
Van - thanks for a very informative video. I see it's been several months since you posted this one, but I hope you don't mind a question now. I see that the fan pressure switch was installed with a tee adapter. I? tried one of those once (JB brand), but couldn't get a good seal and was afraid to keep tightening. Do you use them, and if so is there a trick to getting a good seal? I assume it's just brass against brass with no gasket. thanks a lot

Great video. ...
Great video. Learned something new...Thanks?

good? video.
good? video.

amazing video plz ...
amazing video plz make more for us hvac students that dont pay? any attention in class. very helpfull man great job on the video!

Thanks for the ...
Thanks for the comment. I did not change the switch. I think the refrigerant was migrating to the cooler compressor on the off cycle when the ambient was low (nights & mornings). The compressor may? have tried to start against this liquid. The fuse may have blown because of the high amp draw because of this start up situation. I have installed a crank case heater (the wrap around kind) and shall monitor it. Dave Van West.

Excellent video ...
Excellent video very well done, I guess you? changed the switch?

I use iMovie (Mac) ...
I use iMovie (Mac) to edit my movies, easy to use, I love it. I have not used the Hoffman controls, RPM control is better than stop start, by far. Thanks for the tip will look into them! I proposed a dual mini split for this project. I did not get the work because I was not the "low bidder" w/? dual mini split system design. Guess who has the maint agreement? This GUY (thumbs pointing back at my ownself)! Reliability & Efficiency weren't taken into account by the customer when they chose. Thx

Great video. I just ...
Great video. I just bought a flip cam, so that I can post HVAVR vids. I like the editing what are you using to do that thing at the end? Ever use Hoffman type low ambiant controls? Varies the RPM instead of shutting it off and on - They still ruin motors. If I were to design a system for that room, I would use a mini split. Several cool down? to 5' F or lower without low ambiant controls. Awesome video, keep up the good work.




Bookmark and Share

Privacy Policy | Copyright/Trademark Notification